Schneider Electric C10B32D100 — Miniature Circuit Breakers (MCB)

Schneider Electric C10B32D100 ComPacT NSX100B, 100A, 25kA 41

MPNC10B32D100
Active

Schneider Electric ComPacT NSX series, C10B32D100, 3P 100A circuit breaker with MicroLogic 2.2 electronic trip unit, 25 kA Icu at 415 V AC, IP40.

$252.91 – $523.15Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10B32D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B32D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B32D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B32D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10B32D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B32D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B32D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

The C10B32D100 is a Schneider Electric ComPacT NSX100B molded-case circuit breaker, 3-pole, rated 100 A at 40 °C with a MicroLogic 2.2 electronic trip unit. The MicroLogic 2.2 provides LSoI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). Breaking capacity steps down by voltage: 40 kA at 240 V, 25 kA at 415 V, 20 kA at 440 V, 15 kA at 500 V.

Panel fit and environment

Overvoltage category III suits fixed-installation distribution boards.

Frequently asked questions

What compliance documentation does this brand provide for C10B32D100?

The breaker is certified to EN/IEC 60947-2. It carries an IK07 impact rating and IP40 ingress protection. Standard Schneider Electric declarations for CE marking and applicable directives are available with the product documentation.

MPN
C10B32D100