Skip to main content
Schneider Electric C10R32D100 — Miniature Circuit Breakers (MCB)

C10R32D100 ComPacT NSX100R 3P 100A, 200 kA Icu at 415V AC

MPNC10R32D100
Active

Schneider Electric ComPacT NSX NSX100R, circuit breaker, 3P, 100 A at 40 °C, MicroLogic 2.2 trip unit, 200 kA Icu at 415 V AC, IEC 60947-2.

$1,298.45Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10R32D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10R32D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration3P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10R32D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10R32D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10R32D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10R32D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10R32D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C10R32D100 is a ComPacT NSX100R circuit breaker — a 3-pole, 100 A frame with an electronic MicroLogic 2.2 trip unit. That covers the full curve from a warm motor overload to a dead short. Mounts on a backplate (not DIN rail), wired front-to-front, with a toggle control. IP40 enclosure protection and IK07 impact resistance mean it lives inside a panel, not out on the floor.

The breaker is suitable for isolation per that standard. No RoHS/REACH conflict flagged on the spec record.

Frequently asked questions

Where can I buy C10R32D100 and how do I get a price?

This part is sourced through our independent distribution channel and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is C10R32D100's breaking capacity at 415 V?

200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

What trip unit does the C10R32D100 use?

MicroLogic 2.2 electronic trip unit, providing L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection.

What compliance documentation does this brand provide for C10R32D100?

The breaker is certified to EN/IEC 60947-2 and marked suitable for isolation per that standard.

MPN