The C10R42D040 is a 4-pole ComPacT NSX100R frame circuit breaker with a MicroLogic 2.2 electronic trip unit rated 40 A at 40 °C.
Selectivity and SCCR headroom
At 690 V AC the rating drops to 45 kA Icu, still adequate for 690 V motor circuits. Category A utilization (no intentional short-time delay for selectivity) means this breaker clears fast; coordination with downstream devices relies on the MicroLogic 2.2's adjustable I-t curves, not a delayed trip.
Mounts horizontally or vertically flat on a backplate. Four-pole design with neutral on the left. Five accessory slots available for shunt trips, auxiliary contacts, or communication modules. Connection pitch is 35 mm — standard for panel busbar systems. Dimensions (H x W x D) 161 x 140 x 86 mm fit common enclosure cutouts.