MCCB with MicroLogic 6.2 E — 100 A, 200 kA, LSIG
The C10R46E100 is a Schneider Electric ComPacT NSX100R moulded-case circuit breaker rated 100 A at 40 °C, 4 poles, with a MicroLogic 6.2 E electronic trip unit providing LSIG protection — overload (L), short-time short-circuit (S), instantaneous (I), and ground-fault (G). Its breaking capacity hits 200 kA Icu at 415 V AC 50/60 Hz per IEC 60947-2, which means it can safely interrupt fault currents up to that level without cascading upstream — critical for high-fault panels near large transformers or generators. The electronic trip unit logs time-stamped events, demand values, energy metering, and power quality data, displayed on the integrated LCD.
At 690 V AC the Icu drops to 45 kA, still enough for most industrial step-down transformers.
Mounts on a backplate in horizontal or vertical orientation, flat on the back. Front connections on both upside and downside simplify bus-bar and cable routing in a panel. The 35 mm connection pitch matches standard DIN-rail terminal blocks for auxiliary wiring.