Skip to main content
Schneider Electric C10R46E100 — Residual Current Breakers (RCCB/RCBO)

C10R46E100 ComPacT NSX 100A 4P 200kA MCCB, MicroLogic 6.2 E

MPNC10R46E100
Active

Schneider Electric ComPacT NSX, NSX100R, MCCB, 100 A at 40 °C, 4P, 200 kA Icu at 415 V AC, MicroLogic 6.2 E electronic trip unit, LSIG protection, toggle control, LCD display.

$27.11Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10R46E100 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10R46E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C10R46E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX100R
C10R46E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10R46E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10R46E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

MCCB with MicroLogic 6.2 E — 100 A, 200 kA, LSIG

The C10R46E100 is a Schneider Electric ComPacT NSX100R moulded-case circuit breaker rated 100 A at 40 °C, 4 poles, with a MicroLogic 6.2 E electronic trip unit providing LSIG protection — overload (L), short-time short-circuit (S), instantaneous (I), and ground-fault (G). Its breaking capacity hits 200 kA Icu at 415 V AC 50/60 Hz per IEC 60947-2, which means it can safely interrupt fault currents up to that level without cascading upstream — critical for high-fault panels near large transformers or generators. The electronic trip unit logs time-stamped events, demand values, energy metering, and power quality data, displayed on the integrated LCD.

At 690 V AC the Icu drops to 45 kA, still enough for most industrial step-down transformers.

Mounts on a backplate in horizontal or vertical orientation, flat on the back. Front connections on both upside and downside simplify bus-bar and cable routing in a panel. The 35 mm connection pitch matches standard DIN-rail terminal blocks for auxiliary wiring.

Frequently asked questions

What is the breaking capacity of C10R46E100 at 415 V?

200 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 690 V AC it is 45 kA Icu.

What protection functions does the MicroLogic 6.2 E trip unit provide?

LSIG: overload (L, long-time), short-time short-circuit (S), instantaneous (I), and ground-fault (G) protection.

Where can I buy C10R46E100 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C10R46E100