Skip to main content
Schneider Electric C11F4TM040L — Miniature Circuit Breakers (MCB)

Schneider Electric C11F4TM040L ComPacT NSXm 40A 4P MCCB, 36

MPNC11F4TM040L
Active

Schneider Electric ComPacT NSXm, C11F4TM040L, 40 A 4P MCCB, 36 kA at 415 V AC, TM-D thermal-magnetic trip unit, EN/IEC 60947-2.

$330.67Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F4TM040L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F4TM040L — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F4TM040L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11F4TM040L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11F4TM040L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F4TM040L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F4TM040L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
C11F4TM040L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

MCCB for distribution panels — 40 A, 4-pole, 36 kA

The Schneider Electric C11F4TM040L is a ComPacT NSXm 63F frame moulded-case circuit breaker rated 40 A at 40 °C with a 4-pole (4P) configuration and a TM-D thermal-magnetic trip unit.

Trip curve and selectivity

For a 40 A breaker, the magnetic pickup is typically around 10× In (400 A), which gives good selectivity with downstream 10–20 A MCBs in a lighting or small-power sub-panel. Category A utilisation means it is not intended for motor starting duty — use it on distribution feeders, not direct motor loads.

Mounts on a backplate (not DIN rail) in horizontal or vertical orientation, flat on the back. Front-connect terminals on both line and load sides — no rear-access required. The Everlink lug terminals accept 2.5…95 mm² rigid or stranded aluminium/copper, or 2.5…70 mm² flexible copper. With spreaders, the connection pitch is 35 mm; without spreaders, 27 mm. The 12-module 9 mm pitch footprint (108 mm wide, 137 mm high, 80 mm deep) fits standard enclosure cutouts. Neutral is on the left. IP40 front-face protection and IK07 impact resistance suit enclosed panel installations.

For a BOM line requiring the 40 A 4P NSXm with TM-D trip, the C11F4TM040L is the direct order code — no cross-reference needed.

Frequently asked questions

Where can I buy C11F4TM040L and get a price?

The C11F4TM040L is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is the breaking capacity of C11F4TM040L?

The C11F4TM040L has a performance level F interrupting rating of 36 kA at 415 V AC, per EN/IEC 60947-2.

What terminals does the C11F4TM040L use?

It uses Everlink lug terminals accepting 2.5…95 mm² rigid or stranded aluminium/copper, or 2.5…70 mm² flexible copper.

What compliance standards does C11F4TM040L meet?

The breaker is certified to EN/IEC 60947-2, rated for isolation, pollution degree 3, overvoltage category III, and IP40 / IK07 protection.

MPN