Skip to main content
Schneider Electric C11F4TM100L — Miniature Circuit Breakers (MCB)

Schneider Electric C11F4TM100L ComPacT NSXm 4P 100A MCCB, 36

MPNC11F4TM100L
Active

Schneider Electric ComPacT NSXm 160F, 4P, 100 A thermal-magnetic MCCB, 36 kA at 415 V AC, TM-D trip unit, grey (RAL 7016).

$336.92 – $607.34Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F4TM100L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F4TM100L — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F4TM100L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11F4TM100L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11F4TM100L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F4TM100L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F4TM100L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11F4TM100L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C11F4TM100L is a 4-pole ComPacT NSXm 160F moulded-case circuit breaker rated 100 A at 40 °C with a TM-D thermal-magnetic trip unit.

EN/IEC 60947-2 certifies it for isolation, so you can use it as a disconnecting means without a separate switch.

Deployment context

Backplate-mounted in a distribution panel, the 4-pole 100 A breaker fits 12 module pitches of 9 mm — typical for a three-phase + neutral main incomer. Front terminals accept Everlink lugs up to 95 mm² rigid or 70 mm² flexible copper, which covers standard feeder cables. IP40 is fine for indoor switchboards; IK07 resists light mechanical impact during panel assembly.

Frequently asked questions

What is C11F4TM100L's breaking capacity?

Performance level F: 36 kA at 415 V AC. That is the short-circuit current it can safely interrupt under IEC 60947-2.

What is the closest alternative to C11F4TM100L in this family?

Within the ComPacT NSXm range, the 160A frame (NSXm 160F) shares the same physical footprint and terminal specifications. The trip unit rating is the only difference — choose the 100 A or 160 A variant based on your load current.

Where can I buy C11F4TM100L?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C11F4TM100L