Skip to main content
Schneider Electric C11H3TM063B — Miniature Circuit Breakers (MCB)

Schneider C11H3TM063B ComPacT NSXm MCCB, 63 A, 70 kA

MPNC11H3TM063B
Active

Schneider Electric ComPacT NSXm, C11H3TM063B, 3-pole MCCB, 63 A TM-D trip, 70 kA at 415 V AC, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H3TM063B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H3TM063B — Ratings
ParameterValue
Rated current (In)63 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H3TM063B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H3TM063B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11H3TM063B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H3TM063B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H3TM063B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H3TM063B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

In a 50 °C panel you derate — typical rule of thumb is about 1% per degree above 40 °C. That puts it in the high-breaking range for a 63 A frame; most distribution panels up to 415 V won't need coordination above this. No earth-leakage protection built in, so if you need RCD functionality you add a separate Vigi module or an external RCCB downstream.

Where it goes in the panel

Mounts on a backplate (not DIN rail — the NSXm uses a screw-fixed backplate mount). 9-module pitch at 81 mm wide, 137 mm high, 80 mm deep. Front connection top and bottom for compression lugs or busbars. IP40 front face means it's splash-resistant on the panel door but not washdown-rated. Horizontal or vertical mounting, flat on the back — no derating required for orientation. The flag indicator shows green when auxiliary contacts are present. Connection pitch is 35 mm with spreaders, 27 mm without.

Frequently asked questions

Where can I buy C11H3TM063B and how do I get a price?

C11H3TM063B is sourced through independent distribution channels. Submit an RFQ through our desk; we confirm availability and current pricing at quote time. No stock figures or lead-time numbers on the public page — those are confirmed per inquiry.

What is the closest alternative to C11H3TM063B in the ComPacT family?

Within the same NSXm frame, the closest alternative would be a different trip rating (e.g., 50 A or 80 A TM-D) or a different breaking capacity level (S or L instead of H). No pin-compatible direct drop-in exists with a different rating — the trip unit is integral to the breaker. For a 63 A H-performance 3P, this is the part.

What compliance documentation does Schneider provide for C11H3TM063B?

The breaker is designed to EN/IEC 60947-2, with suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1. IK07 impact resistance and IP40 ingress protection. Standard Schneider documentation includes the IEC declaration of conformity; RoHS and REACH compliance data is available on request through the supply chain.

MPN
C11H3TM063B