Mounts to a backplate, front-connected top and bottom, compression lug or busbar terminations.
Category A utilisation (no intentional short-time delay) so it trips instantaneously on fault; selectivity with downstream breakers relies on the I²t let-through of the TM-D curve, not a delayed trip. 20 000 electrical cycles at 440 V at half rated current, 10 000 at full rated current — that is the endurance for a main breaker that sees infrequent switching.
Backplate-mounted, horizontal or vertical orientation. 12 module pitches at 9 mm each — 108 mm wide, 137 mm high, 80 mm deep. Connection pitch 35 mm with spreaders, 27 mm without. Neutral on the left. IP40 enclosure protection, IK07 impact resistance. Suitability for isolation per IEC 60947-2 — the flag indicator shows auxiliary contact presence.