Skip to main content
Schneider Electric C25B3TM200 — Miniature Circuit Breakers (MCB)

Schneider Electric C25B3TM200 ComPacT NSX Circuit Breaker, 2

MPNC25B3TM200
Active

Schneider Electric ComPacT NSX, circuit breaker, 200 A, 3P, TM-D trip unit, 25 kA at 415 V AC, toggle control, backplate mount.

$330.69Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25B3TM200 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25B3TM200 — Ratings
ParameterValue
Rated current (In)200 A at 40 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25B3TM200 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25B3TM200 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25B3TM200 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25B3TM200 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25B3TM200 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-D trip unit provides thermal overload protection (L) and magnetic short-circuit protection (I). The thermal element tracks the RMS heating of the conductor — it holds 200 A continuously but trips on a sustained overload with an inverse-time curve. The magnetic element responds instantaneously to high fault currents.

The 105 mm width and 161 mm height fit the standard ComPacT NSX cutout. IP40 front face and IK07 impact resistance handle accidental tool drops and panel dust. Five accessory slots accept shunt trips, auxiliary contacts, or under-voltage releases without increasing the footprint.

Frequently asked questions

What is the breaking capacity of C25B3TM200 at 415 V?

The breaking capacity is 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, which is the standard for molded-case circuit breakers in industrial distribution.

What compliance documentation does this brand provide for C25B3TM200?

The breaker is certified to EN/IEC 60947-2 and carries suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1 is specified. For specific RoHS/REACH/UL declarations, request the manufacturer's compliance documentation at quote time.

Where can I buy C25B3TM200 and how is it quoted?

This part is sourced to order through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time, not on a public listing.

MPN