It's a 3-pole, 250 A thermal-magnetic unit (TM-D trip) rated for distribution duty under EN/IEC 60947-2. At 220/240 V it rises to 40 kA; at 500 V it derates to 15 kA — the 415 V figure is the one that governs most European and Asian commercial installations. No earth-leakage module is integrated, so if ground-fault protection is needed, it must be added externally via a Vigi add-on block.
The 161 mm height, 105 mm width, and 86 mm depth fit standard panel cutouts. IP40 front face and IK07 impact resistance suit enclosed panel installation.
Rated current of 250 A at 50 °C. Electrical durability is 20,000 cycles at 440 V at full rated current, and 10,000 cycles at 440 V at In. Power dissipation per pole is 18.75 W, so total heat load for the 3-pole unit is 56.25 W — factor that into enclosure ventilation. Overvoltage category III for fixed-installation switchgear.