The C25H4TM125 is a Schneider Electric ComPacT NSX circuit breaker on the NSX250H frame, 4-pole, with a TM-D thermal-magnetic trip unit rated 125 A at 40 °C. The TM-D provides L (thermal overload) and I (magnetic short-circuit) protection — no earth-leakage module built in, so if you need ground-fault protection you add a Vigi add-on block separately. The 125 A rating sets the continuous current limit for a distribution feeder or large motor branch; at 40 °C ambient it carries full load without derating, but above that you follow the manufacturer's temperature correction curve. Breaking capacity is the headline: 70 kA Icu at 380/415 V AC, 65 kA at 440 V, 50 kA at 500 V, and 35 kA at 525 V. At 240 V it hits 100 kA Icu. Mounts on a backplate, not a DIN rail — the 140 mm width and 161 mm height fit the ComPacT NSX cutout pattern. IP40 enclosure protection means it's fine in a clean panel but not washdown or outdoor without a cover.
Schneider Electric C25H4TM125 ComPacT NSX Circuit Breaker, 1
Schneider Electric ComPacT NSX circuit breaker, NSX250H frame, 4P, 125 A TM-D trip unit, 70 kA Icu at 415 V AC, IP40.
Specifications
| Parameter | Value |
|---|---|
| Product name | ComPacT NSX |
| Product range | ComPacT |
| Product/component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 125 A at 40 °C |
| Poles configuration | 4P |
| Breaking capacity | 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1 |
| Rated service breaking capacity (Ics) | 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz |
| Rated insulation voltage (Ui) | 800 V AC 50/60 Hz |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Utilisation category | Category A |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Electrical durability (cycles) | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Mechanical durability (cycles) | 20000 cycles |
| Parameter | Value |
|---|---|
| Mounting support | Backplate |
| Control type | Toggle |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 0...95 % |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Trip unit protection functions | LI |
Product details
Frequently asked questions
How do I get current pricing and availability for C25H4TM125?
Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.
What is C25H4TM125's breaking capacity at 415 V?
70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it drops to 65 kA, at 500 V to 50 kA, and at 525 V to 35 kA.
What compliance documentation does this brand provide for C25H4TM125?
The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. Pollution degree 3 per IEC 60664-1. The manufacturer provides the usual CE declaration, UL file, and IEC test reports.