At 220/240 V AC it handles 100 kA Icu, and at 690 V AC it still holds 10 kA Icu, so the same breaker can serve a mixed-voltage installation as long as the lowest interrupting rating at the applied voltage exceeds the available fault current. The 4-pole configuration with neutral left and 1 x Ir neutral protection setting means it switches and protects all four poles, suited for three-phase plus neutral distribution. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection curves — the thermal element handles sustained overloads, the magnetic element clears high-current faults instantly.
Mounts on a backplate in horizontal or vertical orientation — flat against the panel, not DIN-rail. Front connections top and bottom, 35 mm connection pitch, 4-pole width of 140 mm, depth 86 mm, height 161 mm. IP40 front face, IK07 impact resistance. Five accessory slots available for shunt trips, auxiliary contacts, or motor operators.