The H breaking capacity code gives you 70 kA Icu at 415 V AC, which is the figure that governs most European 400 V industrial panels; at 240 V it rises to 100 kA, and at 690 V it drops to 10 kA. In a 40 °C panel you get a bit of headroom; in a hot enclosure above 50 °C you need to derate per the manufacturer's curve.
Mounting and integration into a panel
Mounts on a backplate — no DIN-rail clip here. The 4-pole body is 140 mm wide, 161 mm tall, 86 mm deep, with front-front connections (both line and load side). Rated for horizontal or vertical mounting flat on the backplate.
For a BOM line, the 250 A TM-D trip unit and H breaking capacity are the two specs that lock the fit. If your panel is designed around a 250 A NSX250H frame, this order code is the direct drop-in.