Skip to main content
Schneider Electric C25N3MA150 — Miniature Circuit Breakers (MCB)

Schneider Electric C25N3MA150 ComPacT NSX250N, 150A MA Trip,

MPNC25N3MA150
Active

Schneider Electric ComPacT NSX series, NSX250N frame, 3-pole, 150 A magnetic-only MA trip unit, 50 kA Icu at 415 V AC, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C25N3MA150 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C25N3MA150 — Ratings
ParameterValue
Rated current (In)150 A at 65 °C
Poles configuration3P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25N3MA150 — Protection
ParameterValue
Trip unit technologyMagnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25N3MA150 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25N3MA150 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25N3MA150 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25N3MA150 — Specifications
ParameterValue
Trip unit protection functionsI

Product details

The MA trip unit provides magnetic-only short-circuit protection (I), meaning it responds to fault currents but not overloads — the motor's own overload relay handles that. This is standard practice for motor branch circuits where the breaker is sized for the short-circuit rating and the starter provides thermal protection. The 35 mm connection pitch matches standard busbar systems.

Breaking capacity and selectivity headroom

The N breaking capacity code delivers 50 kA Icu at 380/415 V AC and 440 V AC, 36 kA at 500 V, and 35 kA at 525 V per IEC 60947-2. At 480 V AC under UL 60947-4-1 it holds 50 kA. Rated for isolation (EN/IEC 60947-2), pollution degree 3, overvoltage category III. Suitability for isolation means you can use it as a visible-break disconnect for the motor circuit — no separate isolator needed.

Integration notes for the panel

IP40 front face, IK07 impact resistance. Five accessory slots for auxiliary contacts, shunt trips, or under-voltage releases. Electrical durability: 20,000 cycles at 440 V at In/2, 10,000 at full In. Mechanical durability 20,000 cycles. That's typical for a motor-circuit breaker — not a switching device, but rated for occasional isolation and fault clearing.

Frequently asked questions

What is the breaking capacity of the C25N3MA150 at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What is the C25N3MA150 used for?

Motor protection in industrial distribution — the magnetic-only MA trip unit provides short-circuit protection while the motor starter's overload relay handles thermal protection.

What compliance documentation does the C25N3MA150 carry?

Certified to EN/IEC 60947-2, UL 60947-4-1, pollution degree 3 per IEC 60664-1, overvoltage category III, IP40, IK07.

MPN