Skip to main content
Schneider Electric C25R45E100 — Miniature Circuit Breakers (MCB)

Schneider Electric C25R45E100 ComPacT NSX250R, 100 A, 200 kA

MPNC25R45E100
Obsolete

Schneider Electric ComPacT NSX, NSX250R, 4P, 100 A at 40 °C, 200 kA Icu at 415 V AC, MicroLogic 5.2 E electronic trip unit, LCD display, toggle control.

$2,497.97Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25R45E100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25R45E100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25R45E100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25R45E100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25R45E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25R45E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25R45E100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSI

Product details

The C25R45E100 is a Schneider Electric ComPacT NSX250R moulded-case circuit breaker with a MicroLogic 5.2 E electronic trip unit, rated 100 A at 40 °C. The 4P (four-pole) configuration with neutral on the left handles three-phase plus neutral distribution, common in panelboard feeds. Backplate mounting, 161 mm high by 140 mm wide by 86 mm deep — fits standard ComPacT NSX cutouts.

Trip unit and protection logic

The MicroLogic 5.2 E trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection curves. Electronic trip means adjustable settings via the LCD display — no thermal bimetal to drift. The energy meter function logs power quality, time-stamped events, demand current, and maintenance indicators — useful for downstream power monitoring without a separate meter.

Integration notes

Mounts flat on the backplate in horizontal or vertical orientation. Front connections top and bottom simplify busbar or cable routing in a panel. The 35 mm connection pitch matches standard ComPacT NSX accessories. Pollution degree 3 (IEC 60664-1) means it's rated for conductive pollution typical in industrial control panels — no additional conformal coating needed for most environments. IK07 impact rating covers accidental tool drops during commissioning.

Electrical durability at 440 V In (full rated current) is 10,000 cycles; at 440 V In/2 it doubles to 20,000 cycles. At 690 V In/2 it's 10,000 cycles; at 690 V In it's 5,000 cycles. For a distribution breaker seeing infrequent switching (not motor-starting duty), these numbers are well above typical panel life. Category A utilisation means it's not intended for frequent on-load switching of individual loads — it's a distribution breaker, not a motor-starter substitute.

Frequently asked questions

What is C25R45E100's listed range on this component line?

The C25R45E100 belongs to the Schneider Electric ComPacT range, specifically the ComPacT NSX series.

What is C25R45E100's listed depth?

The C25R45E100 has a depth of 86 mm.

MPN