Schneider Electric C25R46E160 — Residual Current Breakers (RCCB/RCBO)

C25R46E160 ComPacT NSX 160A 4P MCCB, MicroLogic 6.2 E, 200 k

MPNC25R46E160
Active

Schneider Electric ComPacT NSX 250R frame, 160 A, 4-pole MCCB with MicroLogic 6.2 E electronic trip unit, 200 kA Icu at 415 V AC, LSIG protection, LCD display, toggle control.

$23.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25R46E160 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25R46E160 — Electrical Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25R46E160 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX250R
C25R46E160 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25R46E160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25R46E160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C25R46E160 is a Schneider Electric ComPacT NSX 250R frame moulded-case circuit breaker, rated 160 A at 40 °C, with a MicroLogic 6.2 E electronic trip unit providing LSIG protection — overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and ground fault (G). It is a 4-pole unit with front connections, a toggle control, and an LCD display for energy metering and event logs.

The 140 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts. Operating altitude is 0–2000 m without derating; above that, derate per the manufacturer's curve.

The MicroLogic 6.2 E trip unit adds ground-fault protection (G) on top of the standard LSIG set, plus energy metering — demand current, power, power quality, time-stamped event tables. This distinguishes it from a basic thermal-magnetic breaker: you get adjustable protection curves, thermal memory (20 min before and after tripping), and communication of data for integration with a building management or SCADA system. The 20000-cycle mechanical durability and 10000-cycle electrical durability at 440 V In give a realistic service life for distribution duty.

Frequently asked questions

What is the breaking capacity of C25R46E160?

The C25R46E160 has a 200 kA Icu at 380/415 V AC (50/60 Hz) per IEC 60947-2. At 690 V AC it is 45 kA Icu. The breaking capacity code is R (200 kA at 415 V AC).

What protection functions does the MicroLogic 6.2 E trip unit provide?

The MicroLogic 6.2 E provides LSIG protection: long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and ground fault (G). It also includes energy metering and communication of data.

Where can I buy C25R46E160 and how is it quoted?

The C25R46E160 is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN
C25R46E160