Skip to main content
Schneider Electric C25V45E100 — Miniature Circuit Breakers (MCB)

Schneider Electric C25V45E100 ComPacT NSX, 100 A, 85 kA Icu

MPNC25V45E100
Obsolete

Schneider Electric, ComPacT NSX series, circuit breaker, C25V45E100, 100 A at 40 °C, 85 kA Icu at 500 V AC, 4P, MicroLogic 5.2 E electronic trip unit.

$16.21Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25V45E100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25V45E100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25V45E100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25V45E100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25V45E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25V45E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25V45E100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSI

Product details

The Schneider Electric C25V45E100 is a ComPacT NSX circuit breaker with a MicroLogic 5.2 E electronic trip unit, rated 100 A at 40 °C. It breaks 85 kA Icu at 500 V AC 50/60 Hz per IEC 60947-2, so it handles high-fault utility feeds or large transformer secondaries without cascading upstream. The 4P (four-pole) construction with left-side neutral suits distribution panels where full isolation of all conductors is required.

Trip unit and protection

The MicroLogic 5.2 E provides L (long-time overload), S (short-time short-circuit), and I (instantaneous) protection curves, plus integrated energy metering. The LCD display shows power quality, demand values, time-stamped event logs, and energy data, which saves panel space by eliminating a separate power meter.

Rated 85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 660/690 V, this breaker sits in the HB1 breaking capacity class.

Mechanical and electrical endurance

Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V In/2, dropping to 10,000 cycles at full rated current 440 V In. At 690 V, half-load switching yields 10,000 cycles; full-load halves that to 5,000. That is typical for a molded-case distribution breaker — it is not a contactor cycled every few seconds, but it handles routine load switching and isolation without premature wear.

Mounting and environment

Mounts on a backplate in horizontal or vertical orientation. Front connections on both upside and downside simplify busbar or cable routing in a panel. IK07 impact rating handles accidental tool drops during maintenance.

Frequently asked questions

How do I get current pricing and availability for C25V45E100?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; pricing and stock are confirmed at quote time.

What is C25V45E100's breaking capacity?

85 kA Icu at 500 V AC 50/60 Hz per IEC 60947-2, derating to 80 kA at 525 V and 75 kA at 660/690 V.

MPN
C25V45E100