Skip to main content
Schneider Electric C63F32M500 — Miniature Circuit Breakers (MCB)

C63F32M500 ComPacT NSX 630F Circuit Breaker, 500 A, 40 kA

MPNC63F32M500
Active

Schneider Electric ComPacT NSX 630F, MCCB, 3P, 500 A at 65 °C, 40 kA Icu at 240 V AC, MicroLogic 2.3 M electronic trip unit, motor protection.

$1,057.12Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C63F32M500 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C63F32M500 — Ratings
ParameterValue
Rated current (In)500 A at 65 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C63F32M500 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C63F32M500 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C63F32M500 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C63F32M500 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C63F32M500 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range250...500 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C63F32M500 is a ComPacT NSX 630F moulded-case circuit breaker (MCCB) with a MicroLogic 2.3 M electronic trip unit, rated 500 A at 65 °C. It is designed for motor protection in three-phase AC networks at 50/60 Hz. That gives selectivity headroom for a downstream feeder without cascading upstream. For a motor-protection application that means the breaker matches the full-load current of a large motor or a group of motors fed through a common bus.

Motor tripping classes 5, 10, and 20 are selectable, letting you match the breaker's overload curve to the motor's thermal withstand. Class 20 is typical for high-inertia loads like fans or centrifuges; class 5 for pumps that start unloaded. The electronic trip unit also provides local signalling: a flashing green LED indicates the breaker is ready to operate; a red LED at 95 % Ith warns of temperature approaching the set point.

IP40 enclosure protection keeps out tools and small debris; IK07 impact resistance handles typical panel-door knocks. Relative humidity range 0...95 % covers non-condensing conditions in unheated electrical rooms.

Frequently asked questions

What is the breaking capacity of C63F32M500 at 415 V?

The C63F32M500 has a breaking capacity of 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

Is C63F32M500 suitable for motor protection?

Yes, the C63F32M500 is designed for motor protection with a MicroLogic 2.3 M electronic trip unit offering selectable motor tripping classes 5, 10, and 20.

What standards does C63F32M500 comply with?

The C63F32M500 complies with EN/IEC 60947-2 and UL 60947-4-1.

What is the rated current of C63F32M500?

The C63F32M500 has a trip unit rating of 500 A at 65 °C.

Where can I buy C63F32M500?

The C63F32M500 is available to order through independent distribution. Submit an RFQ for current pricing and availability.

MPN
C63F32M500