Specifications

EZC250H44150 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250H44150 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]150 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC250H44150 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating150 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250H44150 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth60 mm
EZC250H44150 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250H44150 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2

Product details

Molded case circuit breaker for distribution panels

The Schneider Electric EZC250H44150 is a 4-pole molded case circuit breaker from the EasyPact EZC250H series, rated 150 A at 40 °C with a TM-D thermal-magnetic trip unit. The toggle control gives positive contact indication — no guessing whether it's open or closed. At 380–415 V it handles 36 kA, and at 220–240 V it jumps to 85 kA, so the real limit depends on your system voltage. The IP20 finger-safe enclosure keeps hands out but doesn't seal against water; this is a panel-mounted breaker, not a standalone outdoor unit.

The breaker carries approvals under EN/IEC 60947-1 and EN/IEC 60947-2, the core standards for low-voltage switchgear and circuit breakers. It also meets JIS C8201-2-2 and GB/T 14048.2, covering Japanese and Chinese markets. IK07 impact resistance handles light mechanical shocks during panel assembly.

Mechanical durability and environmental range

Rated for 10,000 mechanical cycles — that's the expected life of the switching mechanism under normal operation, not the electrical endurance at full rated current. The 60 mm depth and 140 mm width fit standard backplate layouts; connection pitch is 35 mm for busbar or cable lug spacing.

Frequently asked questions

What are the key ratings for the EZC250H44150?

Rated current is 150 A at 40 °C with a TM-D thermal-magnetic trip unit. Breaking capacity is 25 kA Icu at 440 V AC, 36 kA at 380–415 V AC, and 85 kA at 220–240 V AC. Insulation voltage is 690 V AC; operational voltage is 550 V AC or 250 V DC.