Skip to main content
Schneider Electric EZC250H44175 — Circuit Breaker Accessories

Schneider Electric EZC250H44175 EasyPact EZC250H 4P 175A Cir

MPNEZC250H44175
Obsolete

Schneider Electric EasyPact EZC250H, molded case circuit breaker, 4 poles, 175 A, thermal-magnetic TM-D trip unit, 85 kA Icu at 240 V AC, 36 kA at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC250H44175 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250H44175 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]175 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC250H44175 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating175 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250H44175 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth60 mm
EZC250H44175 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250H44175 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1

Product details

Specification Summary for Procurement Verification

The Schneider Electric EZC250H44175 is a 4-pole molded case circuit breaker from the EasyPact EZC250H series, rated at 175 A at 40 °C ambient. The thermal-magnetic TM-D trip unit provides overload and short-circuit protection. Breaking capacity is 85 kA Icu at 220–240 V AC, 36 kA at 380–415 V AC, and 25 kA at 440 V AC, all per IEC 60947-2. For DC circuits, it delivers 30 kA Icu at 125 V DC (1P) and 30 kA at 250 V DC (2P).

Standards Compliance and Environmental Ratings

The breaker complies with EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It carries an IP20 degree of protection per IEC 60529 and IK07 impact resistance per EN 50102.

Mounting and Connection Details

The EZC250H44175 is a fixed-mount breaker with backplate support. Both line and load connections are front-facing. Connection pitch is 35 mm. Dimensions: width 140 mm, height 165 mm, depth 60 mm. The toggle control provides positive contact indication.

Application Context and Selectivity Considerations

The breaker is classified as Category A, meaning it is not intended for current-limiting applications requiring Category B performance. Mechanical durability is 10,000 cycles.

Frequently asked questions

Who supplies EZC250H44175 and how is it quoted for volume purchases?

The EZC250H44175 is sourced through independent industrial automation distribution channels. Volume pricing and lead time are confirmed at the time of RFQ submission.

What is the closest alternative to EZC250H44175 in this component family?

Within the EasyPact EZC250H series, the primary variant difference is the breaking capacity code. The EZC250H44175 carries the 'H' (high) breaking capacity code. A lower-breaking-capacity 'N' or 'S' variant would be a parametric alternative, but the H code is the correct selection when the specified fault current levels (85 kA at 240 V AC, 36 kA at 415 V AC) are required per the coordination study.

What compliance documentation does this brand provide for EZC250H44175?

The EZC250H44175 is certified to EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It is suitable for isolation per IEC 60947-2. Standard documentation includes the manufacturer's declaration of conformity and test certificates for the listed standards.

MPN