Skip to main content
Schneider Electric EZS100E3063 — Circuit Breaker Accessories

Schneider Electric EZS100E3063 EasyPact EZS 63A 3P MCCB, 50k

MPNEZS100E3063
Obsolete

Schneider Electric EasyPact EZS, molded case circuit breaker, 63 A, 3P, 50 kA Icu at 240 V AC, thermal-magnetic TM-D trip unit, backplate mount, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZS100E3063 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact EZS
EZS100E3063 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]63 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to EN/IEC 60947-2 400 V AC 50/60 Hz conforming to GB 14048.2
Rated insulation voltage [Ui]690 V conforming to EN/IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to EN/IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZS100E3063 — Protection & Performance
ParameterValue
Breaking capacity50 kA Icu at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380/400 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 17 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 40 kA Icu at 200/230 V AC 50/60 Hz conforming to GB 14048.2 25 kA Icu at 380/400 V AC 50/60 Hz conforming to GB 14048.2
Rated service breaking capacity [Ics]25 kA at 220/230 V AC 50/60 Hz conforming to GB 14048.2 13 kA at 380/400 V AC 50/60 Hz conforming to GB 14048.2 25 kA at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA at 380/400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity codeE
Trip unit technologyThermal-magnetic
Trip unit rating63 A at 40 °C
Trip unit nameTM-D
Protection typeOverload protection (thermal) Short-circuit protection (magnetic)
Suitability for isolationYes
Utilisation categoryCategory A
Mechanical durability13000 cycles conforming to EN/IEC 60947-2 20000 cycles conforming to GB 14048.2
Electrical durability4000 cycles 415 V In/2 conforming to EN/IEC 60947-2 8000 cycles 400 V In conforming to GB 14048.2
EZS100E3063 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEZS100E
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width75 mm
Height130 mm
Depth60 mm
EZS100E3063 — Environmental
ParameterValue
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-35...70 °C
Storage ambient air temperature-50...85 °C
EZS100E3063 — Approvals
ParameterValue
StandardsEN 60947-2 IEC 60947-2

Product details

At 400 V AC the breaking capacity is 25 kA Icu, which still covers the majority of industrial service-entrance and sub-distribution scenarios. The TM-D thermal-magnetic trip unit provides fixed overload protection (thermal) and short-circuit protection (magnetic), with a long-time pickup fixed at 1 In (63 A). This is a no-adjustment design — set the breaker to the cable or load rating and it runs. Rated insulation voltage (Ui) is 690 V, and operational voltage (Ue) is 440 V AC. The IP40 front face and IK07 impact resistance handle accidental tool contact and light mechanical shock during installation.

Mounting is fixed (backplate) with a 25 mm connection pitch — standard for panel-mounted MCCBs. The front-connect design (both upside and downside connections are front) means busbar or cable connections are accessible from the panel face, not the rear. Dimensions are 130 mm height, 75 mm width, 60 mm depth, which fits a standard distribution board cutout. The toggle control provides clear visual indication of tripped vs. ON/OFF status. Electrical durability is 4000 cycles at 415 V In/2 per EN/IEC 60947-2; mechanical durability is 13000 cycles per the same standard. For high-cycle applications (frequent switching of a motor circuit), consider whether the electrical endurance matches the duty cycle.

Frequently asked questions

What are the key ratings of the EZS100E3063?

Rated current 63 A at 40 °C, 3-pole, breaking capacity 50 kA Icu at 240 V AC and 25 kA Icu at 400 V AC per EN/IEC 60947-2, thermal-magnetic TM-D trip unit, rated insulation voltage 690 V, operational voltage 440 V AC.

What compliance documentation does the EZS100E3063 carry?

The breaker is certified to EN 60947-2 and IEC 60947-2. Pollution degree 3 per IEC 60947-1. IP40 and IK07 ratings per IEC 60529 and IEC 62262 respectively. Suitability for isolation is confirmed.

What is the depth of the EZS100E3063?

The depth is 60 mm. Overall dimensions are 130 mm height by 75 mm width by 60 mm depth.

MPN