It's built for distribution duty — overload and short-circuit protection on AC networks — and carries a 50 kA Icu breaking capacity at 220/240 V AC (25 kA at 380/400 V). The 690 V rated insulation voltage and Category A utilisation class mean it's sized for panel feed or sub-feed protection, not motor starting.
The 32 A TM-D trip is fixed — no field-adjustable long-time pickup. That's fine for a dedicated feeder; less flexible if you're trying to squeeze it onto a variable load. At 415 V it drops to 17 kA Icu. The IP40 enclosure and IK07 impact rating suit clean indoor panel mounting — no washdown, no outdoor exposure.
Fixed backplate mount, 25 mm connection pitch, front-facing connections top and bottom. Neutral is on the left. Toggle control, so manual on/off and trip indication are visible through the IP40 cover.