Skip to main content
Schneider Electric GS1DBR3 — Contactors

Schneider Electric GS1DBR3 TeSys GS Fuse Switch Disconnector

MPNGS1DBR3
Obsolete

Schneider Electric TeSys GS series, fuse switch disconnector body GS1DBR3, 3 poles, 32 A rated operational current at 400 V AC-23B, BS fuse type A1 size.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GS1DBR3 — Identification
ParameterValue
Product / component typeFuse switch disconnector body
GS1DBR3 — Contacts & Poles
ParameterValue
Pole configuration3P
GS1DBR3 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 (with terminal cover)
Protective treatment / pollution degreeTH
Fire resistance960 °C body conforming to IEC 60695-2-1
GS1DBR3 — Approvals
ParameterValue
StandardsIEC 60269-1 IEC 60269-2 IEC 60947-3
GS1DBR3 — Mechanical
ParameterValue
Width96 mm
Height98 mm
Depth112 mm

Product details

It's designed to accept BS type fuses in size A1, making it a fused disconnect for motor branch circuits or distribution feeders where the fuse provides the overcurrent protection and the switch provides visible isolation. The 32 A rating at 400 V AC-23B (switching of motors or other high-inductive loads) is the headline number for sizing: it handles motor loads up to 15 kW at 400 V in AC-23 duty. Making capacity is 320 A at the same voltage — the switch can close onto a fault without welding contacts. Short-circuit withstand is 80 kA when protected by the correct BS fuses, so it coordinates with upstream fuses rated for that fault level.

Mounts on a rail or plate — the GS1D footprint is 96 mm wide, 98 mm tall, 112 mm deep. Power connections accept 6 to 25 mm² flexible cable on screw terminals with a control-circuit tightening torque of 3.2 N·m.

Designed and tested to IEC 60269-1, IEC 60269-2, and IEC 60947-3 — the fuse and switch-disconnector standards. Rated insulation voltage 750 V AC, impulse withstand voltage 8 kV. Fire resistance of the body is 960 °C per IEC 60695-2-1. Protective treatment is TH (tropicalized) for humid environments.

Frequently asked questions

What are the key ratings for the GS1DBR3?

Rated operational current 32 A at 400 V AC-23B, breaking capacity 256 A at 400 V AC-23B, making capacity 320 A at 400 V AC-23B, short-circuit withstand 80 kA with BS fuses. Rated power 15 kW at 400 V AC-23.

What standards does the GS1DBR3 comply with?

It complies with IEC 60269-1, IEC 60269-2, and IEC 60947-3. Rated insulation voltage 750 V AC, impulse withstand 8 kV. Body fire resistance 960 °C per IEC 60695-2-1.

What is the physical size of the GS1DBR3?

Width 96 mm, height 98 mm, depth 112 mm. It mounts on a rail or plate. Accepts 6 to 25 mm² flexible cable on screw terminals.

MPN
GS1DBR3