Skip to main content
Schneider Electric GS2GG4 — Contactors

TeSys GS2GG4 Switch-Disconnector-Fuse, 63A, 4P, DIN

MPNGS2GG4
Obsolete

TeSys GS, switch-disconnector-fuse, GS2GG4, 4P, 63 A, DIN fuse size 000, 116.5 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GS2GG4 — Identification
ParameterValue
Product / component typeSwitch-disconnector-fuse
Series / rangeTeSys
GS2GG4 — Contacts & Poles
ParameterValue
Pole configuration4P
GS2GG4 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 (with terminal cover)
Fire resistance850 °C fuse cover conforming to IEC 60695-2-1 960 °C body conforming to IEC 60695-2-1
GS2GG4 — Approvals
ParameterValue
StandardsIEC 60947-3
GS2GG4 — Mechanical
ParameterValue
Width168 mm
Height118 mm
Depth116.5 mm

Product details

The TeSys GS GS2GG4 is a 4-pole switch-disconnector-fuse rated for 63 A at 400 V AC-23B, with a breaking capacity of 500 A at 400 V (AC-23B) and a making capacity of 630 A at 400 V AC-23B. It accepts DIN fuse size 000 and mounts on a plate. The part is designed for isolating and protecting motor circuits and other industrial loads per IEC 60947-3.

The 63 A rating at 400 V AC-23A and AC-23B covers motor switching with frequent on-load operations. For DC loads, it handles 40 A at 440 V with 2 poles in series per phase. Rated operational power is 30 kW at 400 V, 40 kW at 500 V, and 55 kW at 690 V — matching common motor sizes for those voltage levels. The conventional free-air thermal current (Ith) is 63 A at 40 °C, confirming the 63 A rating is not a conditional figure. Short-circuit withstand is 10.6 kA, and the rated short-circuit making capacity (Icm) reaches 100 kA at 400 V when protected by gG fuses. The impulse withstand voltage (Uimp) is 8 kV, and insulation voltage (Ui) is 750 V AC.

The GS2GG4 is listed as obsolete by the manufacturer.

Mounts on a plate (not DIN rail). Dimensions are 168 mm wide, 118 mm high, 116.5 mm deep. Power circuit connections accept lugs or ring terminals from 10 to 25 mm², tightened to 3.2 N·m. The external left-side operating handle allows panel-door mounting. IP20 with terminal cover — suitable for enclosed panel use, not washdown environments.

Frequently asked questions

What are the key ratings for GS2GG4?

Rated operational current is 63 A at 400/500/690 V AC-23A and AC-23B, and 40 A at 440 V DC-23A/B with 2 poles in series. Breaking capacity is 500 A at 400 V AC-23B. Rated power is 30 kW at 400 V, 40 kW at 500 V, 55 kW at 690 V.

What fuse size does GS2GG4 accept?

It accepts DIN fuse size 000.

What standards does GS2GG4 comply with?

It complies with IEC 60947-3 for switch-disconnector-fuse performance. Fire resistance is 850 °C for the fuse cover and 960 °C for the body per IEC 60695-2-1.

MPN
GS2GG4