Skip to main content
Schneider Electric LC2K16107V7 — Contactors

Schneider TeSys K LC2K16107V7 reversing contactor, 3P, 16 A

MPNLC2K16107V7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 400 V AC coil, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC2K16107V7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16107V7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3
LC2K16107V7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16107V7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16107V7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC2K16107V7 is a TeSys K reversing contactor — three-pole, rated AC-3 at ≤440 V for 16 A, with a 400 V AC coil and one normally open auxiliary contact. It comes preassembled with the reversing power busbar, so it's ready to wire into a motor-reversing circuit without extra busbar work. The IP20 finger-safe enclosure (VDE 0106) suits panel-mount installations where personnel access is controlled.

The AC-3 rating at 16 A is the motor-switching duty — that's the figure that governs real use, not a resistive-heater rating. At 690 V AC the contactor can break the circuit, but the motor current limit stays at the AC-3 curve. The 400 V AC coil means it pulls in on a standard 400 V line-to-line control supply; verify your control transformer matches that voltage. The IP20 enclosure is fine inside a panel but offers no washdown protection.

The preassembled busbar saves one wiring step but fixes the pole arrangement; you cannot reconfigure it for non-reversing use.

Flame retardance meets V1 per UL 94 and also complies with NF F 16-101 and NF F 16-102. The protective treatment conforms to IEC 60068 and DIN 50016. Shock and vibration ratings per IEC 60068-2-27 and IEC 60068-2-6 are specified for both closed and open contactor states, which matters for rail or mobile equipment applications.

Frequently asked questions

What is the closest alternative within the TeSys K family?

The TeSys K series includes other reversing contactors with the same footprint and busbar arrangement. The deciding factor is the coil voltage and the current rating — your BOM's coil voltage (400 V AC) and AC-3 current (16 A) must match. Within the same family, a part with a different coil voltage or a higher current rating would require wiring or thermal adjustments.

What is the depth of this contactor?

57 mm, measured from the DIN-rail mounting surface to the front of the housing.

MPN