Skip to main content
Schneider Electric LP2K120045BD — Contactors

Schneider Electric LP2K120045BD TeSys K Changeover Contactor

MPNLP2K120045BD
Active

Schneider Electric TeSys K LP2K120045BD changeover contactor, 4 NO poles, 24 V DC coil, AC-1 utilisation category, IP20, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LP2K120045BD — Identification
ParameterValue
Product / component typeChangeover contactor
Series / rangeTeSys
ApplicationResistive load
LP2K120045BD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1
LP2K120045BD — Contacts & Poles
ParameterValue
Pole configuration4P
LP2K120045BD — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K120045BD — Approvals
ParameterValue
StandardsVDE 0660 IEC 60947 BS 5424 NF C 63-110
LP2K120045BD — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The 20 A thermal current (Ith) at 50 Hz gives the continuous current capacity; the average power-circuit impedance of 3 mOhm keeps voltage drop low under load. Rated breaking capacity reaches 110 A at 440 V, 80 A at 500 V, and 70 A at 660–690 V per IEC 60947, so it clears faults across standard industrial voltages. Mechanical durability is 5 Mcycles, electrical durability 0.3 Mcycles at 20 A AC-1.

Mounts on a rail or plate — the 57 mm depth and 90 mm width fit a standard DIN-rail footprint, leaving room alongside other TeSys K components for a compact reversing starter or source-transfer assembly. IP20 finger-safe terminals (per VDE 0106) mean it can sit in a control cabinet without additional shrouding, though the solder-pin / busbar connection (1.5 x 0.9 mm) expects a specific wiring method — not a screw-clamp terminal.

Compliance documentation includes VDE 0660, IEC 60947, BS 5424, and NF C 63-110. The insulation system is rated 600 V per UL 508 and CSA C22.2 No 14, and 690 V per IEC 60947-4-1 for the power circuit.

Frequently asked questions

What are the key ratings for this contactor?

AC-1 utilisation category, 4 NO poles, 24 V DC coil, 20 A thermal current (Ith), 3 mOhm average impedance, breaking capacity up to 110 A at 440 V, and mechanical durability of 5 Mcycles.

What compliance documentation does this brand provide for LP2K120045BD?

The part complies with VDE 0660, IEC 60947, BS 5424, and NF C 63-110. Insulation ratings are 600 V per UL 508 and CSA C22.2 No 14, and 690 V per IEC 60947-4-1.

MPN
LP2K120045BD