Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NC, 12 V DC coil, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LP2K12017JD — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationResistive load Motor control
LP2K12017JD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-1 AC-4
LP2K12017JD — Contacts & Poles
ParameterValue
Pole configuration3P
LP2K12017JD — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP2K12017JD — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Rated AC-3 at 12 A up to 440 V, it switches motor loads in that current band; the AC-1 rating covers resistive loads at the same current level.

Vibration withstand of 4 Gn closed, 2 Gn open per IEC 60068-2-6, and shock ratings (15 Gn closed on Z axis) mean it holds in on high-vibration lines like conveyor drives or compressor skids.

Flame retardance rated V1 per UL 94, with additional compliance to NF F 16-101 and NF F 16-102 (railway fire behaviour). Protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance. Utilisation categories AC-1, AC-3, and AC-4 cover resistive, motor starting, and plugging/inching duty respectively.

Frequently asked questions

What is the closest alternative to LP2K12017JD in the same family?

Within the TeSys K series, the LP2K12017JD is the reversing contactor variant with a 12 V DC coil. The standard non-reversing contactor with the same coil voltage is the LC1K12017JD; the reversing busbar and mechanical interlock are pre-integrated on the LP2K, so swapping to two LC1Ks plus external interlocks would take more panel space and wiring. If the coil voltage can change, the LP2K12017JD has siblings with 24 V DC, 48 V DC, and 110 V AC coils — verify your control voltage before substituting.

What is the depth of the LP2K12017JD?

57 mm depth (body only, excluding coil terminals). Combined with 90 mm width and 58 mm height, it fits a standard 200 mm deep enclosure with room for wiring.

What compliance documentation does Schneider provide for this part?

The part carries UL 94 V1 flame rating, IEC 60068 environmental testing, and NF F 16-101/102 railway fire compliance. Standard Schneider documentation includes the datasheet (with wiring diagrams), a user manual, and a declaration of conformity covering the CE mark. RoHS and REACH declarations are available through the Schneider portal.

MPN