Skip to main content
Schneider Electric MGN25133 — Miniature Circuit Breakers (MCB)

MGN25133 C60H MCB, 3P D-curve 25A, 30kA Icu

MPNMGN25133
Obsolete

Schneider Electric Multi9 C60H series, MGN25133 miniature circuit breaker, 3-pole, D-curve, 25 A rated current, 30 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25133 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN25133 — Ratings
ParameterValue
Rated current (In)25 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration3P
Number of protected poles3
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN25133 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN25133 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width54 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches6
MGN25133 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN25133 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric MGN25133 is a C60H miniature circuit breaker from the Multi9 range, a 3-pole thermal-magnetic unit with a D-curve and a 25 A rating at 50 °C per EN/IEC 60947-2. Rated operational voltage is 440 V AC, with a breaking capacity of 30 kA Icu at 240 V AC phase-to-phase and 15 kA Icu at 415 V AC — that's the maximum fault current it can safely interrupt without welding its contacts or rupturing the case. Service breaking capacity Ics is 50 % of Icu at each voltage level — 15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V — meaning after one fault at that level the breaker is still functional enough to hold the line until you swap it out.

MPN