Skip to main content
Schneider Electric MGN25139 — Miniature Circuit Breakers (MCB)

MGN25139 C60H MCB, 4P D-curve 2 A, 30 kA

MPNMGN25139
Obsolete

Schneider Electric C60H Multi9 miniature circuit breaker, MGN25139, 4-pole, D-curve, 2 A rated current, 30 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25139 — Identification
ParameterValue
Product nameC60
Product rangeMulti9
Product range (series)C60
Product/component typeMiniature circuit-breaker
Device applicationDistribution
MGN25139 — Ratings
ParameterValue
Rated current (In)2 A at 50 °C conforming to EN/IEC 60947-2
Poles configuration4P
Number of protected poles4
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated operational voltage (Ue)440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
MGN25139 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles conforming to EN/IEC 60947-2
Mechanical durability (cycles)20000 cycles
MGN25139 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width72 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches8
MGN25139 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
Pollution degree3 conforming to EN/IEC 60947-2
MGN25139 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric MGN25139 is a C60H Multi9 miniature circuit breaker (MCB) with 4 protected poles, a D-curve trip characteristic, and a 2 A rated current at 50 °C per EN/IEC 60947-2. It's built for distribution boards where high inrush loads — motor starters, transformers, or lighting ballasts — need a magnetic trip threshold of 12 x In (±20 %) to avoid nuisance tripping on startup.

Rated Icu of 30 kA at 240 V AC phase-to-phase, 15 kA at 415 V, and 10 kA at 440 V. The Ics (service breaking capacity) is 50 % of Icu at each voltage level — 15 kA, 7.5 kA, and 5 kA respectively. That means after clearing a fault at the Ics level, the breaker is still usable, though you'd want to verify its condition before returning it to service. For a 2 A D-curve on a 4-pole frame, this gives solid headroom for downstream coordination in a 240 V or 415 V distribution panel.

The 4-pole body takes 8 x 9 mm pitches (72 mm wide). IP20 finger-safe terminals suit enclosed panel mounting. Separate earth-leakage block (Vigi) can be added on the load side for RCD protection.

Listed as current production. The C60H series is a long-running Multi9 platform; the MGN25139 is the standard catalog number for the 2 A D-curve 4P variant. Compliance documentation covers EN/IEC 60947-2, pollution degree 3, and isolation suitability.

Frequently asked questions

What is the breaking capacity of MGN25139?

30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V, and 10 kA at 440 V, all per EN/IEC 60947-2. The Ics is 50 % of Icu at each voltage.

Where can I buy MGN25139 and how is it quoted?

MGN25139 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the closest alternative to MGN25139 in the C60 family?

Within the C60 range, the C60N series offers a lower breaking capacity (typically 10-15 kA at 240 V) compared to the C60H's 30 kA. If you need the same 4-pole D-curve 2 A but can accept lower fault current ratings, a C60N variant would be the direct alternative. For higher interrupting capacity, the C60L series goes to 50 kA at 240 V.

What compliance documentation does Schneider provide for MGN25139?

The MCB is certified to EN/IEC 60947-2, with pollution degree 3 and isolation suitability per that standard. The Multi9 range typically carries CE, UKCA, and EAC markings; specific RoHS and REACH declarations are available from Schneider's documentation portal.

MPN
MGN25139