Skip to main content
Schneider Electric VW3A46156 — AC Drive (VFD) 480V

Schneider Electric VW3A46156 Passive Filter, 395A, 480V, 60H

MPNVW3A46156
Obsolete

Schneider Electric Altivar series, passive filter VW3A46156, 395 A output, 480 V, 60 Hz, THDI 10 % for ATV61/71 drives up to 500 kW/700 hp, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

VW3A46156 — Identification
ParameterValue
Product typePassive filter
VW3A46156 — Input / Supply
ParameterValue
Rated supply voltage range480 V +/- 10 %
Network number of phases3 phases
VW3A46156 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20 IP55 (enclosure mounting)
VW3A46156 — Environmental
ParameterValue
Operating ambient temperature45...60 °C (with current derating 3 % per °C) 5...45 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C storage in original packaging -25...65 °C during transport
Vibration resistance2 mm peak to peak (f= 5...13.2 Hz) conforming to IEC 60068-2-6 0.7 gn (f= 13.2...150 Hz) conforming to IEC 60068-2-6
VW3A46156 — Approvals
ParameterValue
Standards complianceIEC 61000-2-2 IEC 61000-2-4 IEC 61000-3-12 G5/4 engineering recommendation IEC 61000-3-2 IEC 61000-3-4

Product details

The Schneider Electric VW3A46156 is a passive filter designed to reduce current harmonics on Altivar ATV61 and ATV71 variable speed drives rated up to 500 kW / 700 hp. It handles a continuous output current of 395 A at a supply voltage of 480 V ±10 %, 60 Hz, three-phase. Two of these filters are required per drive for the target motor ratings. THDI sits at 10 % for the listed drive-and-motor combinations, which keeps harmonic injection within IEC 61000-3-12 and G5/4 engineering recommendation limits. Efficiency is 98 %, with thermal losses of 1175 W — that heat has to go somewhere, so factor it into your enclosure ventilation. Power factor varies with load: cos φ is 1 at 150 % of line current, 0.99 at 100 %, and 0.85 at 75 %. The filter can handle 1.5× nominal current for 60 seconds — useful for short-duration overloads during startup or transient events.

IP20 base rating; IP55 when enclosure-mounted. The filter uses A/B terminals with 2.5 mm² capacity for the control connections and X1-1…X2-3 terminals accepting 25…300 mm² for the power wiring. Mounting altitude derating kicks in above 1000 m — 5 % current reduction per 1000 m up to 4000 m. Operating temperature range is 5…45 °C without derating, 45…60 °C with a 3 % per °C derating. Vibration resistance per IEC 60068-2-6: 2 mm peak-to-peak at 5…13.2 Hz, 0.7 gn at 13.2…150 Hz. Insulation class F. Storage temperature in original packaging is -25…55 °C; transport range extends to -25…65 °C.

Frequently asked questions

What THDI does the VW3A46156 achieve?

The VW3A46156 delivers 10 % THDI for ATV61H, ATV71H, ATV61Q, and ATV71Q drives paired with a 500 kW / 700 hp motor.

What standards does the VW3A46156 comply with?

It complies with IEC 61000-2-2, IEC 61000-2-4, IEC 61000-3-12, G5/4 engineering recommendation, IEC 61000-3-2, and IEC 61000-3-4.

What is the power factor of the VW3A46156 at different load levels?

Cos φ is 1 at 150 % of line current, 0.99 at 100 %, and 0.85 at 75 % of line current.

MPN