Mechanical and mounting
The 3RT1056-6AR36-0UA0: The contactor measures 172 mm high by 120 mm wide by 170 mm deep, and mounts via screw fixing with a vertical mounting surface that is rotatable ±90° and tiltable ±22.5° to front and back. The enclosure clearance requirements are 10 mm upward, 10 mm downward, 20 mm forward, and 10 mm at the side — tight enough for a standard 600 mm deep panel with gland plate clearance.
Termination and conductor ranges
The main power circuit accepts stranded conductors from 25 to 120 mm². The coil and auxiliary terminals accept solid or stranded conductors: 2× (0.5 to 1.5 mm²), 2× (0.75 to 2.5 mm²), or max 2× (0.75 to 4 mm²). The auxiliary switch is present on this variant.
Coil and switching performance
The coil operates at 24 VDC with a rated holding current of 10 A at 24 V. The contactor is rated for up to 800 operations per hour at AC-1, 750/h at AC-3, and 300/h at AC-2 duty.