Siemens SIRIUS 3RT1056-6NP38-0PA5 – Size S6 Power Contactor, 200–277 V Coil
It measures 172 mm high, 120 mm wide, and 170 mm deep, and mounts by screw fixing on a vertical surface with ±90° rotation and ±22.5° tilt allowed.
Switching Capability and Duty Cycles
Maximum switching frequency varies by duty: 800 operations per hour under AC-1 (resistive), 750/h under AC-3 (squirrel-cage motor starting), 300/h under AC-2 (slip-ring motor), and 130/h under AC-4 (plugging/inching).
The main power circuit accepts stranded conductors from 25 to 120 mm²; the auxiliary/control circuit accepts solid or stranded wires in two sizes per terminal: 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), or max 2x (0.75–4 mm²). An auxiliary switch is included, and the contactor has a mechanical service life of 10 million operations typical.