The contactor measures 45 mm wide, 102 mm high, and 97 mm deep, and mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715. It is designed for standing installation on a horizontal surface.
The 24 VDC coil draws 0.25 A at 50 Hz and 0.28 A at 60 Hz — a tight range that keeps the control transformer sizing predictable across line frequencies. The contactor's switching frequency varies by duty: up to 1000 cycles/hour at AC-1 (resistive loads), 750 at AC-2 and AC-3 (motor starting/running), and 250 at AC-4 (plugging/inching). For AC-3e (enhanced motor starting) it's also 750 cycles/hour.
Integration notes
The spring-type terminals accept solid or stranded wire 1–10 mm², or 2x (0.5–2.5 mm²) for daisy-chaining. Arcing time is 10 ms, so coordination with upstream fuses or breakers should account for that let-through energy.