Mounting and spacing
The 3RT2028-1AC20: Fastens to 35 mm DIN rail per DIN EN 60715. Required clearances: 10 mm upwards, 10 mm downwards, 10 mm forwards, and 6 mm at the side. Mounting position allows ±180° rotation on a vertical surface and ±22.5° tilt forward/backward. Arcing time is 10 ms. For auxiliary contact wiring, the terminals accept 2x (0.5–1.5 mm²) or 2x (0.75–2.5 mm²) solid or stranded conductors.