SIRIUS S0 power contactor — panel integration notes
The 45 mm width and 85 mm height fit standard S0 panel layouts, with a 141 mm depth that leaves clearance for front-of-panel wiring access. Switching frequency varies by duty class: up to 1,000 cycles/hour at AC-1 (resistive loads), 750 cycles/hour at AC-2 and AC-3 (motor starting/running), and 250 cycles/hour at AC-4 (plugging/inching). For AC-3e duty, the same 750 cycles/hour applies. The arcing time is 10 ms at AC, which informs coordination with upstream protective devices.
Wiring and clearance
Main contacts accept solid or stranded conductors from 1 to 10 mm²; auxiliary contacts accept 2x (0.5 to 1.5 mm²) solid or 2x (0.75 to 2.5 mm²) stranded. These clearances are for arc flash and heat dissipation — maintain them in the panel layout.