SIRIUS S3 contactor for motor switching
The screw-type terminals on both main and auxiliary circuits accept 2x (0.5...1.5 mm²) solid or stranded, or 2x (0.75...2.5 mm²) finely stranded with ferrules — a practical range for motor branch circuits up to the contactor's rating.
The DC magnet coil draws 0.7 W during closing and holds at 0.29 W — low enough for direct PLC output drive without an interposing relay in most cases. The control circuit terminals are screw-type, same as the main circuit, keeping your wiring tooling consistent across the panel. Rated surge voltage resistance is 6 kV, which aligns with IEC 60947-1 coordination for industrial environments.
Environmental and protection ratings
Operating temperature range is -10 to +55 °C, storage from -25 to +70 °C.