Siemens 3RW5072-6AB15 Soft Starter, 90 A, 200-600 V, ATEX

MPN3RW5072-6AB15
Active

Siemens 3RW5072-6AB15 soft starter, 90 A minimum rated current, 200-600 V operating voltage, Class 10A/10E/20E, ATEX, UKEX, IECEx, UL, CSA, 160 x 230 x 282 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5072-6AB15 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5072-6AB15 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)110 kW
Rated motor power at 230 V (40 °C)55 kW
Rated operational current at 40 °C210 A
Rated operational current at 50 °C186 A
Rated operational current at 60 °C170 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)1 867 W
3RW5072-6AB15 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
3RW5072-6AB15 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5072-6AB15 — Mechanical
ParameterValue
Height230 mm
Width160 mm
Depth282 mm
Weight7.3 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5072-6AB15 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; derating as of 1000 m, see Manual
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5072-6AB15 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (preset) / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases2
Utilization category according to IEC 60947-4-2AC-53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
Ramp-Down Time Of Soft Starter0 ... 20 s
3RW5072-6AB15 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Trip class and motor protection

The 3RW5072-6AB15: Trip class is selectable between CLASS 10A, 10E (preset), and 20E per IEC 60947-4-2. CLASS 10A suits standard induction motors with short acceleration times; CLASS 20E handles high-inertia loads like centrifuges or crushers where the start current must be sustained longer without nuisance tripping. The minimum load setting is 15 % of the smallest settable Ie, which allows the soft starter to protect lightly loaded motors without false overcurrent trips. A service factor of 1 means no built-in overload margin beyond the set current — the trip threshold matches the motor FLA exactly.

Fieldbus and control integration

Onboard fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP, plus PROFIenergy support when paired with the PROFINET communication module. This lets the starter participate in energy-management schedules and coordinated start sequences without a separate gateway. The analog output is configurable as 4-20 mA or 0-10 V (default 4-20 mA), parameterizable via the High Feature HMI. Remote reset is achieved by cycling the control supply voltage — no separate reset signal needed.

Mounting and thermal derating

Dimensions are 160 mm wide, 230 mm high, and 282 mm deep, with screw fixing to the mounting plate. Clearance requirements: 100 mm upward, 75 mm downward, 10 mm forward, 5 mm sideways, and 0 mm backward — the back can sit flush against the panel backplate. In a sealed enclosure with multiple drives, plan for forced ventilation or a larger cabinet to stay below the derating threshold.

Compliance and sourcing

No direct cross-reference to the alternate MPNs listed in the catalog — verify panel wiring before substituting.

Frequently asked questions

What ATEX and UKEX approvals does this soft starter carry?

ATEX, UKEX, and IECEx are all listed as Yes, suitable for Zone 2/22 hazardous-area motor circuits.