Skip to main content
Siemens 3RW5227-3AC15 — Soft Starters

Siemens 3RW5227-3AC15 SIRIUS Soft Starter, 40.5 A, 200-600 V

MPN3RW5227-3AC15
Active

Siemens SIRIUS 3RW5227-3AC15 soft starter, 40.5 A minimum, 200-600 V rated, Class 10A/10E/20E, screw fixing, 306x185x203 mm.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5227-3AC15 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5227-3AC15 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)45 kW
Rated motor power at 230 V (40 °C)22 kW
Rated operational current at 40 °C161 A
Rated operational current at 50 °C143 A
Rated operational current at 60 °C131 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)1 077 W

Control & Connection

3RW5227-3AC15 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebox terminal
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5227-3AC15 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5227-3AC15 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight6.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5227-3AC15 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5227-3AC15 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5227-3AC15 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Trip class and motor starting duty

The 3RW5227-3AC15 ships with a default trip class of CLASS 10A per IEC 60947-4-2, with selectable 10E and 20E curves for heavier starting loads like crushers or centrifuges where the acceleration time exceeds 10 seconds. Minimum load setting is 15% of the smallest settable Ie, so it handles lightly loaded motors without nuisance tripping on the start curve.

Mounting and panel clearance

Screw-fixing mount with a vertical surface orientation; the unit is rotatable ±90° and tiltable ±22.5° front-to-back, giving flexibility in tight enclosures. Clearance requirements are 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, and 0 mm backwards — plan the gland plate and cable duct accordingly. Overall dimensions are 306 mm height, 185 mm width, 203 mm depth — fits standard 600 mm deep enclosures with room for the main contactor and overload above or below.

Communication and control integration

Built-in PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard interfaces mean it drops into most plant networks without a separate gateway. PROFIenergy support is available when paired with the PROFINET communication module, allowing coordinated energy management during idle phases. Analog output is configurable as 4-20 mA (default) or 0-10 V via the High Feature HMI, giving the PLC a direct current or voltage signal proportional to motor current.

Environmental and compliance

Shock resistance is 15 g / 11 ms, dropping to 12 g / 11 ms if contact lifting is a concern — suitable for most industrial environments without additional vibration damping. Carries CE, UL, and CSA approvals, covering installations under IEC, North American, and Canadian codes without separate agency review.

Frequently asked questions

What is 3RW5227-3AC15 used for?

It is a SIRIUS soft starter for three-phase induction motors, providing controlled acceleration and deceleration to reduce mechanical stress and inrush current. Typical applications include pumps, conveyors, fans, and compressors where the trip class (10A/10E/20E) matches the starting duty.

MPN
3RW5227-3AC15