Siemens 3RW5513-3HA14 — Soft Starters

Siemens 3RW5513-3HA14 Soft Starter, 200-480 V, ATEX

MPN3RW5513-3HA14
Active

Siemens 3RW5513-3HA14 soft starter, 200-480 V rated, ATEX, IECEx, trip class 10A/10E/20E/30E, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, 170 mm width, 275 mm height, 152 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5513-3HA14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5513-3HA14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)5.5 kW
Rated motor power at 230 V (40 °C)3 kW
Rated operational current at 40 °C22.5 A
Rated operational current at 50 °C19.9 A
Rated operational current at 60 °C18.2 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)166 W
3RW5513-3HA14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5513-3HA14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5513-3HA14 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.3 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5513-3HA14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5513-3HA14 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5513-3HA14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What this soft starter delivers that a basic starter cannot

The 3RW5513-3HA14 is a Siemens soft starter rated for 200-480 V motor supply, with trip class options 10A, 10E (default), 20E, or 30E per IEC 60947-4-2. That trip class range means you can match the overload protection to the motor's thermal capacity and starting duty — a pump with a long acceleration time gets 30E, while a fast-starting conveyor stays at 10A. It carries ATEX and IECEx certification, so it is approved for installation in explosive atmospheres — not just a general-purpose starter. The control supply accepts 110-250 V at 50 or 60 Hz, which covers most plant auxiliary voltages without a separate transformer. Fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFIenergy. That means it integrates into a PLC-based line without a gateway — the same part handles both discrete and networked control.

Mounting and panel integration — clearances that matter

The unit measures 170 mm wide, 275 mm high, and 152 mm deep. Forced-air clearance: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and zero behind. That zero-backwards clearance means it can sit flush against the back panel — no wasted depth. Solid wire connections accept 2x (1.0-2.5 mm²) and 2x (2.5-10 mm²) per terminal. No screw terminals — the connection method is not listed as screw type, so expect spring-cage or push-in; verify the termination style from the product drawing before wiring.

Soft-start features for pump and conveyor duty

Voltage ramp and pump ramp down let you tailor acceleration and deceleration to the load — a pump gets a soft stop to avoid water hammer, a conveyor gets a controlled start to prevent product shift. Torque control and breakaway pulse handle high breakaway torque loads like crushers or mixers. DC braking and motor heating are built in — DC braking stops the motor quickly without a mechanical brake, and motor heating keeps windings dry in humid environments. Analog output can be set to 4-20 mA or 0-10 V for feeding motor current or power to a PLC or panel meter. Service factor 1.15 means the starter can handle 115% of rated current continuously — useful when the motor is oversized or running at the edge of its thermal limit.

Diagnostics and lifecycle management

Event list, error logbook, and trace function are standard — these record start/stop events, fault history, and parameter changes, which helps with root-cause analysis on a tripped line. Firmware update capability means the unit can be upgraded in the field without replacing hardware. Accuracy class 5 per IEC 61557-12 applies to the measurement functions — current and voltage readings are within 5% of true value, adequate for monitoring but not for billing-grade metering.

Frequently asked questions

What is the ATEX rating on this soft starter?

The 3RW5513-3HA14 carries ATEX certification (Yes) and IECEx certification (Yes), meaning it is approved for use in explosive atmospheres per the respective standards.

What trip classes does this soft starter support?

It supports trip classes 10A, 10E (default), 20E, and 30E per IEC 60947-4-2. The class is parameterizable to match the motor's thermal overload protection profile.

What are the mounting clearances required for this unit?

Clearances: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind. The unit is 170 mm wide, 275 mm high, and 152 mm deep.

What compliance documentation does Siemens provide for 3RW5513-3HA14?

The part carries CE marking, UL approval, and CSA approval. RoHS and REACH documentation is typically provided by Siemens upon request.

MPN
3RW5513-3HA14