Skip to main content
Siemens 3UG4832-2AA40 — Process / Temperature Controllers

Siemens 3UG4832-2AA40 SIRIUS Voltage Monitoring Relay, 10-60

MPN3UG4832-2AA40
NRND

Siemens SIRIUS 3UG4832-2AA40 voltage monitoring relay, digital setting, LCD, 10-600 V AC/DC, IP20, snap-on mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3UG4832-2AA40 — Identification
ParameterValue
Product functionVoltage monitoring relay
Product designationVoltage monitoring relay with digital setting
Product line / brand nameSIRIUS
3UG4832-2AA40 — Communication
ParameterValue
Electrical connection typespring-loaded terminals
3UG4832-2AA40 — Environmental
ParameterValue
Ingress protection (IP rating), wiredIP20
Installation altitude, max.2 000 m
3UG4832-2AA40 — Mechanical
ParameterValue
Fastening methodsnap-on mounting
Mounting positionany
Width22.5 mm
Height94 mm
Depth91 mm
Conductor cross-section, solid24 ... 16
Conductor cross-section, finely stranded (with ferrule)0.25 ... 1.5 mm²
Mounting clearance, top0 mm
Mounting clearance, rear0 mm
Mounting clearance, side0 mm
Mounting clearance, front0 mm

Product details

The Siemens 3UG4832-2AA40 is a SIRIUS voltage monitoring relay with digital setting and an LCD display, designed to watch AC or DC supply rails from 10 V up to 600 V (measurable voltage at AC and DC, both 10... 600 V). It catches both overvoltage and undervoltage conditions (overvoltage detection yes, undervoltage detection yes), and offers an adjustable start-up delay of 0... 999.9 s to ride through inrush dips. The relay auto-resets once the voltage returns to the window, and an external reset input is available for manual intervention. The 22.5 mm width keeps the footprint tight — one standard module wide. IP20 protection class IP20 is fine for a dry control cabinet; no washdown rating here.

The 10-600 V AC/DC range covers common control voltages (24 VDC, 120 VAC, 230 VAC, 480 VAC) and even some medium-voltage signal levels. The relative repeat accuracy of 1 % means the trip point won't drift more than 1 % from the set value over temperature and time — tight enough for most motor protection and generator monitoring schemes. The storage and transport range of -40 to +85 °C covers cold-weather shipping. Degree of pollution 2 is the standard for a dry, non-conductive-dust cabinet.

Frequently asked questions

What voltage range does this relay monitor?

It monitors AC or DC voltages from 10 V to 600 V (measurable voltage at AC 10... 600 V, measurable voltage at DC 10... 600 V).

What is the mounting width and style?

It snaps onto a 35 mm DIN rail (snap-on mounting) and is 22.5 mm wide — one standard module. Any mounting position is allowed.

Does it have an LCD display?

Yes, it has an LCD display (design of the display LCD) for local readout of voltage and settings.

MPN
3UG4832-2AA40