What this MCCB carries for a panel build
The 3VA1010-2ED32-0CH0: Three poles, line-protection duty, fitted with a TM210 thermal-magnetic release. That's a standard motor-starting and distribution profile; it coordinates well downstream of a larger MCCB or upstream of a fused disconnect. Breaking capacity is voltage-dependent: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. The 690 V rating confirms it can serve 600 V class systems as well.
Integrated auxiliaries and releases
That means three separate signal paths: two for status feedback (open/closed) and one dedicated to trip indication, which can drive a remote alarm or PLC input without sharing contacts.
The 76.2 mm width is a standard 3-pole MCCB footprint — three 25.4 mm pole centers — so it fits existing SENTRON 3VA mounting bases and busbar systems without adapter plates. Depth of 70 mm leaves room behind the door for wiring gutters or a second row of terminal blocks.