Skip to main content
Siemens 3VA1010-2ED32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED32-0CH0 SENTRON MCCB, 100 A, 3-Pole, Line

MPN3VA1010-2ED32-0CH0

Siemens SENTRON 3VA1010-2ED32-0CH0, molded case circuit breaker, 3-pole, 100 A, TM210 release, line protection, with undervoltage release, 2 aux + 1 alarm switch.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-2ED32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA10102ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1010-2ED32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
3VA1010-2ED32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1010-2ED32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED32-0CH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB carries for a panel build

The 3VA1010-2ED32-0CH0: Three poles, line-protection duty, fitted with a TM210 thermal-magnetic release. That's a standard motor-starting and distribution profile; it coordinates well downstream of a larger MCCB or upstream of a fused disconnect. Breaking capacity is voltage-dependent: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. The 690 V rating confirms it can serve 600 V class systems as well.

Integrated auxiliaries and releases

That means three separate signal paths: two for status feedback (open/closed) and one dedicated to trip indication, which can drive a remote alarm or PLC input without sharing contacts.

The 76.2 mm width is a standard 3-pole MCCB footprint — three 25.4 mm pole centers — so it fits existing SENTRON 3VA mounting bases and busbar systems without adapter plates. Depth of 70 mm leaves room behind the door for wiring gutters or a second row of terminal blocks.

Frequently asked questions

What is the breaking capacity of 3VA1010-2ED32-0CH0 at 415 V?

32 kA at 415 V, which is the standard test voltage for IEC 60947-2 MCCB ratings. At 240 V it reaches 52.5 kA, and at 690 V it still interrupts 7.5 kA.

What auxiliary contacts come with this MCCB?

Two auxiliary switches plus one trip alarm switch (HQ type), providing separate NO/NC status feedback and a dedicated alarm signal on trip.

Where can I buy 3VA1010-2ED32-0CH0?

This part is sourced to order through independent industrial distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

Will 3VA1010-2ED32-0CH0 drop into a panel specified for 3VA1010-2ED32-0JA0?

Both share the same 100 A frame, TM210 release, and 3-pole 76.2 mm footprint, so the mechanical fit is identical. The difference is in the auxiliary contact configuration and the undervoltage release — verify those match your schematic before substituting.

MPN
3VA1010-2ED32-0CH0