Siemens 3VA1010-2ED32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED32-0AE0 SENTRON MCCB, 100 A, 52.5 kA at 2

MPN3VA1010-2ED32-0AE0

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA1010-2ED32-0AE0, 3-pole, 100 A rated continuous current, TM210 thermal-magnetic trip unit, 52.5 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-2ED32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-2ED32-0AE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1010-2ED32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED32-0AE0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What the 100 A rating and TM210 trip unit mean for your panel

The Siemens SENTRON 3VA1010-2ED32-0AE0 is a 3-pole molded case circuit breaker (MCCB) rated for a continuous current Iu of 100 A at 40 °C, with no derating needed up to 50 °C — it holds the full 100 A at 50 °C. Above that, the thermal curve steps down: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. This matters for a panel that runs warm; you don't lose headroom until the ambient passes 50 °C. The TM210 overcurrent release is a fixed thermal-magnetic trip — no electronic adjustment, no communication function, no voltage trigger, and no phase-failure detection. It's a straight line-protection device for standard feeder or distribution duty where you don't need selectivity tuning or remote monitoring.

Breaking capacity — the voltage-dependent curve

Breaking capacity varies sharply with system voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. For a 480 V panel (common in North America) the relevant figure is the 415 V or 440 V rating — expect around 32 to 13.6 kA depending on your exact line voltage. That's adequate for most secondary distribution but not for high-fault utility entrance positions.

Auxiliary contacts and panel integration

Frequently asked questions

Where can I buy 3VA1010-2ED32-0AE0 and how do I get a price?

This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current pricing and availability; the quote confirms the delivery position.

What is the breaking capacity of this MCCB at 415 V?

At 415 V AC the breaking capacity is 32 kA. At 440 V it drops to 13.6 kA, and at 690 V to 7.5 kA.

Does this breaker include a shunt trip or undervoltage release?

No. This variant has no undervoltage release, no shunt trip, and no ground-fault monitoring. It ships with four auxiliary switches (HQ type) for status feedback.

What is the thermal derating above 50 °C for the 3VA1010-2ED32-0AE0?

The breaker holds 100 A continuously up to 50 °C. At 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A.

MPN
3VA1010-2ED32-0AE0