Skip to main content
Siemens 3VA1010-2ED42-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED42-0AE0 SENTRON MCCB, 100 A, 4-Pole, 52.5

MPN3VA1010-2ED42-0AE0

Siemens SENTRON 3VA1010-2ED42-0AE0, molded case circuit breaker, 4-pole, 100 A rated continuous current, TM210 thermal-magnetic release, 52.5 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-2ED42-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-2ED42-0AE0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED42-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED42-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED42-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1010-2ED42-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED42-0AE0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens 3VA1010-2ED42-0AE0 is a 4-pole SENTRON molded case circuit breaker rated for 100 A continuous current at 40 °C, with a TM210 thermal-magnetic release for line protection. Its interrupting capacity hits 52.5 kA at 240 V and 32 kA at 415 V — enough headroom for most industrial distribution panels without cascading upstream. Four HQ auxiliary switches are built in, so you can wire status feedback or shunt-trip monitoring without adding a separate block.

Interrupting capacity across voltage levels

This MCCB delivers 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. That spread covers common low-voltage distribution voltages in North America (240/480 V) and IEC markets (400/415 V). At 690 V the 7.5 kA rating is sufficient for motor branch circuits with limited fault current — check your system's available fault current against these numbers for selectivity coordination.

At 55 °C it holds 96 A, at 60 °C it holds 94 A, at 65 °C it holds 92 A, and at 70 °C it holds 90 A.

Frequently asked questions

What is the interrupting capacity of 3VA1010-2ED42-0AE0 at 240 V?

52.5 kA at 240 V, with 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

Where can I buy 3VA1010-2ED42-0AE0?

This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What is the rated continuous current of 3VA1010-2ED42-0AE0?

100 A at 40 °C, with no derating needed up to 50 °C. At 55 °C it holds 96 A, at 60 °C 94 A, at 65 °C 92 A, and at 70 °C 90 A.

MPN
3VA1010-2ED42-0AE0