Skip to main content
Siemens 3VA1040-3ED32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1040-3ED32-0CA0 SENTRON MCCB, 40A, 3-Pole, 75.6kA

MPN3VA1040-3ED32-0CA0

Siemens SENTRON 3VA1040-3ED32-0CA0, Molded case circuit breaker, 3-pole, 40 A, 75.6 kA at 240 V AC, undervoltage release, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1040-3ED32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10403ED320AA0
3VA1040-3ED32-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.13.3 W
3VA1040-3ED32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1040-3ED32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1040-3ED32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1040-3ED32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1040-3ED32-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1040-3ED32-0CA0 is a 3-pole molded case circuit breaker (MCCB) rated 40 A at 40 °C, with a breaking capacity of 75.6 kA at 240 V AC.

Breaking capacity drops from 75.6 kA at 240 V to 52.5 kA at 415 V, then 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. At 415 V, 52.5 kA is enough for most industrial service-entrance and sub-distribution boards — you have headroom for selective coordination with downstream 18–25 kA MCCBs. At 690 V, the 7.5 kA rating limits this breaker to low-fault branches or transformer-fed loads.

Thermal derating and ambient limits

Rated 40 A from 40 °C through 50 °C, then derates to 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C.

Undervoltage release and auxiliary options

The UVR is factory-fitted; no field-kit installation. No voltage-trigger or communication function on this order code.

The 76.2 mm width (3 inches) matches the standard SENTRON 3VA1 3-pole footprint — fits existing DIN-rail or panel-mount cutouts without re-drilling. Power loss at rated load is 13.3 W maximum, so no special ventilation required in a standard IP40 enclosure.

Frequently asked questions

Where can I buy 3VA1040-3ED32-0CA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1040-3ED32-0CA0 at 415 V?

At 415 V AC, the breaking capacity is 52.5 kA. At 240 V it's 75.6 kA, at 440 V it's 32 kA, and at 500 V and 690 V it's 7.5 kA.

Does 3VA1040-3ED32-0CA0 include an undervoltage release?

Yes, this variant includes a factory-fitted undervoltage release (UVR) as the auxiliary release, used for undervoltage protection or emergency-stop circuits.

What is the closest functional second-source for 3VA1040-3ED32-0CA0?

The 3VA1110-5ED32-0AA0 is a higher-current sibling in the same SENTRON 3VA1 family — check the amp rating and breaking capacity at your system voltage before substituting. Footprint and pole count are the same, but the overcurrent release and UVR configuration may differ.

MPN
3VA1040-3ED32-0CA0