Skip to main content
Siemens 3VA1040-3ED32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1040-3ED32-0CH0 SENTRON MCCB, 40 A, 3-Pole, Line

MPN3VA1040-3ED32-0CH0

Siemens SENTRON 3VA1040-3ED32-0CH0, molded case circuit breaker, 3-pole, 40 A rated continuous current (Iu), TM210 thermal-magnetic release, line protection version, with undervoltage release and 2 aux + 1 trip alarm switch HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1040-3ED32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1040-3ED32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C38.4 A
Current at 60 °C37.6 A
Current at 65 °C36.8 A
Current at 70 °C36 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1040-3ED32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1040-3ED32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1040-3ED32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1040-3ED32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1040-3ED32-0CH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1040-3ED32-0CH0 — SENTRON MCCB, 40 A, Line Protection

The interrupting ratings climb to 75.6 kA at 240 V and 52.5 kA at 415 V, so it handles high-fault-current scenarios common in industrial switchgear. No communication function, no phase failure detection, and no ground fault monitoring are built in; this is a straightforward thermal-magnetic MCCB without electronic trip unit extras.

Above that, it derates: 38.4 A at 55 °C, 37.6 A at 60 °C, 36.8 A at 65 °C, and 36 A at 70 °C.

Interrupting Ratings Across Voltages

The interrupting capacity varies sharply with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. For a 415 V panel with typical transformer impedance, 52.5 kA covers most service-entrance and sub-feed applications.

That 76.2 mm width is a standard 3-pole MCCB footprint — it drops into the same panel cutout as other 3VA 3-pole frames. The IP40 front protection means it's rated for indoor panel mounting only; no outdoor or washdown exposure.

Frequently asked questions

What is the interrupting capacity of 3VA1040-3ED32-0CH0 at 415 V?

52.5 kA at 415 V. At 240 V it's 75.6 kA, at 440 V it's 32 kA, and at 690 V it's 7.5 kA.

Where can I buy the 3VA1040-3ED32-0CH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does this breaker include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release, plus a 2-auxiliary-switch + 1-trip-alarm-switch HQ contact block.

MPN