Skip to main content
Siemens 3VA1050-4ED46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1050-4ED46-0AA0 SENTRON MCCB, 50 A, 4-Pole, TM210

MPN3VA1050-4ED46-0AA0
Active

Siemens SENTRON 3VA1050-4ED46-0AA0, molded case circuit breaker, line protection, 4-pole, 50 A (Iu), TM210 overcurrent release, breaking capacity 121 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1050-4ED46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1050-4ED46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C48 A
Current at 65 °C46 A
Current at 70 °C45 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.14.6 W
3VA1050-4ED46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1050-4ED46-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1050-4ED46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1050-4ED46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1050-4ED46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, and 52.5 kA at 440 V; at 500 V and 690 V it holds at 11.9 kA — making it suitable for high-fault utility feeds or downstream of large transformers. The thermal derating from 45 °C to 70 °C is mild: 50 A at 45 °C and 50 °C, 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C — no need to oversize for typical panel ambient up to 50 °C.

Width is 101.6 mm (4 in), depth 70 mm (2.76 in), height 130 mm (5.12 in). No integrated communication function or motor drive option — this is a standalone breaker for manual or remote shunt-trip operation.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

At 415 V the breaking capacity is 75.6 kA, which covers most industrial secondary-distribution fault levels.

Where can I buy 3VA1050-4ED46-0AA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What thermal derating applies at higher panel temperatures?

At 45 °C and 50 °C the breaker carries 50 A; at 55 °C it derates to 49 A, at 60 °C to 48 A, at 65 °C to 46 A, and at 70 °C to 45 A. For a panel running at 50 °C, no derating is needed.

MPN
3VA1050-4ED46-0AA0