Skip to main content
Siemens 3VA1080-3ED32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-3ED32-0BC0 SENTRON MCCB, 80 A, 3-Pole, 52.5

MPN3VA1080-3ED32-0BC0

Siemens SENTRON 3VA1080-3ED32-0BC0, molded case circuit breaker, 3-pole, 80 A, TM210 overcurrent release, 52.5 kA breaking capacity at 415 V, undervoltage release, 2 HQ auxiliary switches.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1080-3ED32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1080-3ED32-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1080-3ED32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1080-3ED32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1080-3ED32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1080-3ED32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1080-3ED32-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1080-3ED32-0BC0 is a 3-pole molded case circuit breaker (MCCB) rated for 80 A continuous current (Iu) and designed for line protection in distribution panels and motor control centers. Breaking capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — the 415 V figure is the one most commonly checked for European 400 V distribution.

The 80 A rating holds at ambient temperatures up to 50 °C — no derating needed in a typical 40 °C panel. Above that, current must be reduced: 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C. Operating ambient range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Auxiliary and Undervoltage Release Configuration

No voltage trigger or phase-failure detection is built in.

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth. The 76.2 mm width is a standard 3-pole MCCB footprint for DIN-rail or screw-mount panels — verify gland-plate cutouts against the existing backpanel layout.

Frequently asked questions

Will 3VA1080-3ED32-0BC0 drop into a panel specified around 3VA1010-2ED42-0AE0 without rewiring?

The 3VA1080-3ED32-0BC0 is a different frame size and rating — 80 A vs the 3VA1010 family's lower current. Panel cutouts and busbar spacing may differ. Verify the mounting footprint and terminal centers before substituting without a panel rework.

MPN
3VA1080-3ED32-0BC0