Skip to main content
Siemens 3VA2110-5JP32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JP32-0DA0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2110-5JP32-0DA0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2110-5JP32-0DA0, 3-pole, 100 A rated continuous current, line protection design with undervoltage release and communication function.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2110-5JP32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21105JP320AA0
3VA2110-5JP32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W
3VA2110-5JP32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-5JP32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5JP32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-5JP32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5JP32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens 3VA2110-5JP32-0DA0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed as the panel warms up. Its 3-pole design handles line protection duty, with a rated insulation voltage of 800 V and breaking capacities that scale with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

Panel fit and thermal performance

Dimensions are 86 mm deep, 105 mm wide, and 181 mm tall — a standard 3-pole MCCB footprint for DIN-rail or panel-mount installation. Power loss is 12.5 W maximum, which is modest for a 100 A frame and keeps internal panel temperature rise manageable in a sealed enclosure. Operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C. The continuous current rating holds flat at 100 A from 40 °C through 70 °C — no thermal derating curve to calculate for typical industrial panel environments.

Frequently asked questions

What is the breaking capacity of 3VA2110-5JP32-0DA0 at different voltages?

Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The 187 kA rating at 240 V makes it suitable for high-fault-current distribution panels.

Does 3VA2110-5JP32-0DA0 require derating at elevated ambient temperatures?

No derating is needed — the 100 A continuous current rating holds flat from 40 °C through 70 °C ambient, simplifying panel design in warm environments.

Where can I buy 3VA2110-5JP32-0DA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
3VA2110-5JP32-0DA0