Skip to main content
Siemens 3VA2110-5JQ32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-5JQ32-0AD0 SENTRON MCCB, 100 A, 3-pole, ETU5

MPN3VA2110-5JQ32-0AD0

Siemens SENTRON 3VA2110-5JQ32-0AD0, molded case circuit breaker, 3-pole, 100 A, ETU560 electronic trip unit, line protection, 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2110-5JQ32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-5JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2110-5JQ32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.10 W
3VA2110-5JQ32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
3VA2110-5JQ32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-5JQ32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2110-5JQ32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-5JQ32-0AD0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

For a packaging line running multiple motor starters and heater loads off one feeder, the ETU560 lets you coordinate selectively with downstream breakers so a single fault doesn't drop the whole machine. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. At 415 V — common for European three-phase distribution — 121 kA covers most industrial transformer ratings without needing a current-limiting upstream fuse. If your panel sits near ovens or in a non-conditioned enclosure, that derating curve tells you the real ampacity without guessing.

Trip unit and protection logic

That saves panel space and wiring compared to add-on ground-fault modules. For a line that tracks uptime and fault events, this avoids a separate monitoring relay. Three auxiliary switches (HQ type) are integrated for remote status indication — open/closed, tripped, and ground-fault alarm. No separate auxiliary contact block needed.

Keep it inside a locked panel, not on the machine surface.

Frequently asked questions

What is the breaking capacity of 3VA2110-5JQ32-0AD0 at 415 V?

121 kA at 415 V, which is the same rating as at 440 V. At 240 V it reaches 187 kA.

Does 3VA2110-5JQ32-0AD0 include ground-fault protection?

Yes, the ETU560 trip unit provides ground-fault monitoring via summation current formation on the L-conductor, no external CT required.

Where can I buy 3VA2110-5JQ32-0AD0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2110-5JQ32-0AD0