Siemens 3VA2110-8HK42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-8HK42-0AA0 SENTRON MCCB, 100 A, 4-Pole, ETU3

MPN3VA2110-8HK42-0AA0
Active

Siemens SENTRON 3VA2110-8HK42-0AA0, molded case circuit breaker, 4-pole, 100 A rated continuous current, ETU340 electronic trip unit, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2110-8HK42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2110-8HK42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.7.7 W
3VA2110-8HK42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
3VA2110-8HK42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-8HK42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-8HK42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-8HK42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

The Siemens 3VA2110-8HK42-0AA0 is a 4-pole SENTRON molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel thermal budgeting in a crowded enclosure. The ETU340 electronic trip unit gives you adjustable N-conductor protection (OFF, 50%, or 100%) and a fixed long-time delay of 1500 ms, so coordination studies can rely on a known trip curve without field tweaks. Breaking capacity hits 440 kA at 240 V and still holds 53 kA at 690 V, meaning this breaker clears high-fault scenarios on the line side without cascading upstream.

The breaker measures 140 mm wide by 181 mm tall by 86 mm deep, so it fits standard SENTRON 3VA panel cutouts and busbar systems. Four-pole construction means it occupies the same footprint as a 3-pole plus a neutral pole in a single molded case — no add-on neutral module required.

Selectivity and coordination — where the 440 kA matters

With 440 kA interrupting capacity at 240 V and 330 kA at 415 V, this MCCB can sit directly downstream of a main breaker or transformer without needing a current-limiting fuse upstream for fault clearance. The ETU340's fixed 1500 ms long-time delay gives predictable coordination with downstream 3VA feeders or branch breakers — useful when a site electrical engineer is building a selective coordination study per NEC 240.86 or IEC 60947-2.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-8HK42-0AA0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the depth of 3VA2110-8HK42-0AA0?

The depth is 86 mm (3.4 in), measured from the mounting surface to the front of the breaker.

What compliance documentation does Siemens provide for 3VA2110-8HK42-0AA0?

As a SENTRON MCCB, this breaker carries Siemens' standard declaration of conformity for the Low Voltage Directive, plus CE marking for the European market. Specific documentation (RoHS, REACH, UL file) is available on request at quote time.

Will 3VA2110-8HK42-0AA0 drop into a panel specified around 3VA1010-2ED32-0JA0?

Not without checking the cutout and busbar arrangement. The 3VA2110 is a 4-pole 100 A frame with an ETU340 trip unit, while the 3VA1010 is a 3-pole 100 A frame with a different trip curve. The 4-pole version is physically wider — verify the panel's pole spacing and neutral bar provision before substituting.

MPN